▶Power supply : 24V DC (11 ÷ 36V DC), power consumption: 2.5 W max.
▶Display : ?none or graphic LCD, 128 x 64 points, with backlight
▶Type of probe : radial integrated, length 40 mm,Ø 18 mm, stainless steel 316L, PTFE filter cap
▶Probe parameters : Temp.measuring range (-30 ~ +80 °C) Humidity measuring range (0 100% RH)
▶Number of inputs : 0 or 1 universal
=> Current: 0/4-20 mA
=> Voltage: 0/1-5 V, 0/2-10V,
=> RTD: Pt100, Pt500, Pt1000 ( Measuring range: -100°C ÷ 600°C )
=> Thermocouple: type K, S, J, T, N, R, B, E ; Measuring ranges: -200°C ÷ +1370°C (K); -50°C
÷ +1768°C (S); -210°C ÷ +1200°C (J); -200°C ÷ +400°C (T; -200°C ÷ +1300°C (N); -50°C
÷ +1768°C (R); +250°C ÷ +1820°C (B); -200°C ÷+1000°C (E)
▶ Accuracy: 0.1%@25°C ± one digit( inputs:current, voltage, milivoltage, thermoresistance, thermocouple K,J,E) ;
0.2%@25°C(thermocouple N); 0.5%@25°C (thermocouple S, T, R, B)
▶Analogue outputs (0, 1 or 2 ) : active current: operating range 0/4-20 mA (0-24 mA max.); passive current: isolated,
operating range 4-20 mA (2.8-24 mA max.); active voltage: operating range 0/1-5V,
0/2-10V (0-11V max.)
▶Communication interface : RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU, not galvanically isolated
▶Operating temperature : -30°C ÷ +80°C,case with electronics (out of range -20 ÷ +70°C LCD and IR receiver turn off)
▶Protection class : IP 67 (version without display); IP 65 (version with display)
▶Case : wall mounted, 120 x 90 x 50 mm, material: ASA LURAN + polycarbonate